Three Phase Power Quality Analyzer

Order Code: 22236235.107

Category: General Lab Equipment II

Voltage Transients Measurement range  ±8 kV Sampling rate: 1775: 1 MS/s 1777: 1 MS/s, 20 MS/ Bandwidth: DC to 1 MHz Trigger Adjustable trigger level. Triggers on high-frequency components > 1.5 kHz Resolution:14-bit synch...



SPECIFICATION

Voltage Transients

  • Measurement range  ±8 kV
  • Sampling rate: 1775: 1 MS/s 1777: 1 MS/s, 20 MS/
  • Bandwidth: DC to 1 MHz
  • Trigger Adjustable trigger level. Triggers on high-frequency components > 1.5 kHz
  • Resolution:14-bit synchronous sampling

Current inputs

  • Number of inputs: 4 inputs 3 phases and Neutral, range selected automatically to attached sensor
  • AC: 4 inputs 3 phases and Neutral, range selected automatically to attached sensor
  • 1 A to 1500 A with i17XX-FLEX1500 12 
  • 1 A to 1500 A with i17XX-FLEX1500 24
  • A to 3000 A with i17XX-FLEX3000 24
  • 6 A to 6000 A with i17XX-FLEX6000 36
  • 40 mA to 40 A with clamp i40s-EL
  • 4 A to 400 A with clamp i400s-EL
  • DC: 20 A to 2000 A with 80i-2010-EL clamp
  • Bandwidth : DC to 30 kHz
  • Resolution: 24-bit synchronous sampling
  • Sampling frequency: 80 kS/s at 50/60 Hz
  • Scaling:1:1, variable
  • Input voltage clamp: 50 mV / 500 mV rms; CF 2.8 Rogowski Coil: 15 mV / 150 mV rms at 50 Hz, 18 mV / 180 mV rms at 60 Hz; CF 4 all at nominal probe range
  • Input impedance:11 kΩ

Aux Inputs

  • Wired connection with 17xx-AUX adapter
  • Number of inputs: 2
  • Input range direct: 0 V dc to  ± 10 V dc
  • Input impedance direct: 2.92 MΩ
  • Scale factor Scale factor format: mx + b (gain and offset) user configurable
  • Displayed units user configurable (up to 8 characters, for example °C, psi, or m/s)
  • Input mains frequency DC, 50/60 Hz ±15 % (42.5 Hz … 57.5 Hz, 51 Hz … 69 Hz)
  • Topologies: 1-φ, 1-φ IT, Split phase, 3-φ delta, 3-φ wye IT, 3-φ Aron/Blondel (2 element delta), 3-φ delta open leg, 3-φ high leg delta
  • Data storage: 8 GB internal (expandable with microSD card)
  • Memory size: Typical 10 logging sessions of 8 weeks with 1-minute intervals and 100 events. The number of possible logging sessions and logging period depends on user requirements
  • Real-time accuracy Internal: 3 ppm (0.26 s per day, 8 s per month) NTP (internet time): Depending on internet latency, typical < 0.1 s absolute to UTC
  • ? GPS: < 1 ms absolute to UTC

Trend interval

  • Measured parameter
  • Trend interval user selectable: 1 sec, 3 sec, 5 sec, 10 sec, 30 sec, 1 min, 5 min, 10 min, 15 min, 30 min
  • Averaging interval min/max values Voltage, Current: ½ cycle RMS (20 ms at 50 Hz, 16.7 ms at 60 Hz) Aux, Power: 200 ms
  • Total harmonic distortion THD for voltage and current is calculated on 50 harmonics

Power quality measurements

  • Measured parameter harmonics h0 … h50 % fund and RMS for voltage, current and power Phase angles for voltage and current up to h11 Inter-harmonics ih0… ih50 % fund and RMS for voltage and current
  • Super-harmonics
  • 2–9 kHz with 200 Hz bins
  • 9–30 kHz with 2 kHz bins
  • RMS for voltage and current
  • Grouped, sub-grouped and single harmonic bins according to IEC 61000-4-7.
  • Method selected automatically based on configured PQ standard or user configurable
  • Total harmonic distortion
  • Calculated on up to 50 harmonics (depends on selected PQ standard
  • Mains signaling Mains signaling
  • 2 frequencies in the range from 110 Hz to 3000 Hz
  • Events
  • Voltage
  • Dip, swell, interruption, rapid voltage change, mains signaling, wave shape deviation, transients
  • Current
  • Inrush current
  • Triggered recording
  • Half cycle RMS of voltage and current for 10 s
  • Waveform of voltage and current for 10/12 cycles
  • Mains signaling: 200 ms RMS of mains signaling voltage up to 120 s
  • Transients: Waveform of voltage 