Order Code: 23246730.4
Category: General Lab Equipment II
• Protective relay control station • DC power supply: Input voltage: 240/415v AC, 3-phase • Output voltage: 120V • Output current: 5A
Specification:
• Protective relay control station
• DC power supply :Input voltage: 240/415v AC, 3 phase
• Output voltage: 120V
• Output current: 5A
• AC power supply: Input voltage: 240/415v AC, 3 phase
• Output voltage: 110V, 220V, 400V
• Output current: 5A at 110V, 10A at 220V, 10A at 400V
• Current sensitivity relay module
• Current metering range: 0.4 ~ 6A
• Input current: 8A
• Hysteresis range: 5% to 50% of selected current
• Output contact: 10A at 250VAC
• Operating voltage: 220V AC, 2.5A
• Three phase under over/voltage relay module
• Nominal input voltage: 69V or better option, line to neutral
• Maximum input voltage: 120% of nominal input voltage
• Under voltage set point range: 75% to 100% of nominal input voltage
• Over voltage set point range: 100% to 125% of nominal input voltage
• Hysteresis range: 1% to 15% of nominal input voltage
• Output contact: 2 x SPDT, 5A at 240v AC
• AC/DC volt sensitivity relay module
• Voltage metering range: 40 to 600v
• Maximum input voltage: 650v
• Hysteresis range: 5% to 50% of selected metering range
• Output contact: 8A at 250v AC
• Operating voltage: 240v, AC
• Under/over frequency relay module
• Nominal frequency: 50Hz
• Nominal input voltage:120v
• Maximum input voltage: 120% 0f nominal input voltage
• Frequency range: 40 t0 60 Hz
• Synchronizing limit adjustment range: 0.1 to 3.0 Hz
• Output contact: 2 x SPDT, 5A at 240v AC
• Synchro-check relay module
• Nominal input voltage:120v
• Minimum input voltage: 70% of nominal input voltage
• Maximum input voltage: 130% of nominal input voltage
• Frequency range: 45 to 65 Hz
• Synchronizing limit adjustment range: 10% to 30% of nominal input voltage
• Phase balance/sequence relay module
• Nominal input voltage: 120v, line to line
• Minimum input voltage: 120% of nominal input voltage
• Unbalance set point range: 5% to 15% of nominal input voltage
• Time delay range: 0.5 to 10 seconds
• Output contact: DPDT, 5A at 240v AC
• Reverse power relay module
• Nominal input voltage: 69v AC
• Minimum input voltage: 120% of nominal input voltage
• Nominal input current: 5A AC
• Maximum input current: 200% of nominal input current
• Reverse power set point range: 2% to 20%
• Time delay range: 0 to 20 seconds
• Output contact: DPDT, 5A at 240v AC
• Electromechanical relay module
• Nominal input voltage: 220v AC
• Minimum input voltage: 10% of nominal input voltage
• Maximum input voltage: 10% of nominal input voltage
• Maximum current: 300mA
• Auxiliary switching option: NO & NC
• Output contact: TPST, 16A at 450V
• Motor power factor relay module
• Nominal input voltage: 415v, 3 phase
• Minimum input voltage: 90% of nominal input voltage
• Maximum input voltage: 110% of nominal input voltage
• Minimum input current: 0.5A AC
• Maximum input current: 6A AC
• Power factor set point range: 0 to 0.9
• Start delay range: 0 to 20 seconds
• Output contact: SPDT, 10A at 250v AC
• Work station: All module in a portable single station
• Probes: 25pcs, Max load 15A