Surface Pump

Order Code: 21225302.1

Category: General Lab Equipment I

Front suction multi stage horizontal shall Electrical driven surface pump Q=15 Us, total head=95m ,P=22KW, a motor of 380/400V,50hz , pump efficiency at duty point =65% .impeller and diffuser made of stainless steel(AISI 306) or bronze and shaft m...



SPECIFICATION

  • Front suction multi stage horizontal shall Electrical driven surface pump Q=15 Us, total head=95m ,P=22KW, a motor of 380/400V,50hz , pump efficiency at duty point =65% .impeller and diffuser made of stainless steel(AISI 306) or bronze and shaft made of stainless steel(AISI 420) and accessories, with star delta control panel starting system.   Accessories:- Foot valve one pcs, Counter flange out lat one pcs, Counter flange in lat one pcs, seal Electrode 2pcs and standard accessories 

General

  • Surface pump directly coupled to electrical motor 
  • Min -permissible sand contentment water 25 girnI 
  • Temperature minimum 30t 
  • Total system head 95 meter 
  • Discharge 15 liter per second 
  • Power 22 kilo watt 
  • Pump set efficiency shall be not less than 65 % 

1. Pump 

  • Multistage, Centrifugal type 
  • Horizontal directly coupled to the motor 
  • Pump material  Pump shaft Stainless steel (AISI 420)  Impeller Stainless steel ( 306) or Bronze (CuSnI0) Diffuser Stainless steel/ Bronze 

2. Motor 

  • Electrical motor of adtpuite pow 380/400v, three phase. 50HZ 
  • Designed as to facilitate rewinding in field workshop 
  • Motor materials Component  Shaft- for Standard water well Stainless Steel AISI 300 Series  Stator- Stainless Sled AISI 300 Series  Bushings- Bronze / Stainless Steel 
  • Overheating protection device in the motor winding shall be available (optional)

3. Starting Methods 

  • Star delta  Control panel board 
  • Three phase, 4 wires, 380/400v,50Hz . 
  • Short-Circuit protected wity.a MCCB 
  • Systems over current protection relay which is adjustable according to load.  

Water level monitoring relay for dry running  protection - Voltmeter with selector switch for phase voltage.

  • Ammeter for phase current measurment.
  • Indicator lamps for pump running, fault, and mains
  • Phase faliure relay.
  •  Electrodes or water level control
  • Fuse holders and fuse for auxiliary circuit protection.
  • Start and stop push button
  • Manual or automatic selector switch
  • Time delay relay
  • Temperature sensor relay for overheating protection of motor
  • Metallic enclosure with IP 45

4. Additional Equipment
 All standard accessories as per the manufacture's recommendation but at least  should include.

  • Water level sensor electrode 3 Pcs.
  • Instruction manual 
  • Suction counter flages with bolts and nuts one set.
  • Delivery counter flanges with bolts and nuts one set.
  • Foot valve(for Negative suction head)

5. Technical Information
Pump discharge and total head Complete pump performances at duty point and at different heads and discharge

  • Pump HP/KW 
  • Pump efficiency at 0.8 power factor
  • Number of stages total length of pump and motor
  • Outlet connection diameter
  • Type of impeller
  • Impeller pump shaft, motor and pump casing material 
  • Make and type or starter
  • Control panel box full detail
  • Other relevant information
     

Enquiry Form