Secondary Current Injector Relay Test set

Order Code: 19203364.9

Category: General Lab Equipment III

Technical Specification:  AC current source: Amplitude range: 6*(0-30A)  Accuracy: 0.1%  Six-phase current parallel output max: 180A  Phase current long-term allowable working values: 10A  Power: 300VA...



SPECIFICATION

Technical Specification: 

  1. AC current source:
    1. Amplitude range: 6*(0-30A) 
    2. Accuracy: 0.1% 
    3. Six-phase current parallel output max: 180A 
    4. Phase current long-term allowable working values: 10A 
    5. Power: 300VA / phase 
  2. DC current source: 
    1. Amplitude: 20A 
    2. phase power: 300VA 
    3. phase accuracy: 0.2%
  3. AC voltage source: 
    1. Amplitude range: 6*(0--125V) 
    2. Accuracy: 0.1% 
    3. Line voltage range: 0--250V 
    4. Phase voltage / line voltage Output power: 70VA / 100VA 
  4. DC voltage source: 
    1. Phase voltage output amplitude: 0-- ± 150V 
    2. Accuracy: 0.2% 
    3. Line voltage output amplitude: 0-- ± 300V 
    4. Phase voltage / line voltage Output power: 90VA / 180VA 
  5. DC auxiliary voltage source, + 110V (0.6A).
  6. Switch Terminals: 
    1. Switch input terminals: 8 pairs 
    2. Air access point: 1--20mA, 110V internal device active 
    3. Potential flip: 0--6VDC low 15--250VDC high 
    4. Switch output terminals: four pairs of empty contacts, breaking capacity: 110V / 2A, 220V / 1A
  7. Time measurement range: 1ms ~ 9999s accuracy 1ms 
  8. Frequency range: 0--1000Hz Accuracy: 0.001Hz 
  9. Phase: 0--360 ° Accuracy: 0.1 ° 
  10. Power source: AC220V ± 10% 50Hz 10A 

Enquiry Form