Primary Current Injection kit

Order Code: 21225144.1

Category: General Lab Equipment I

Name of The Manufacturer: To be mentioned  Address of the Manufacturer: To be mentioned  Model: To be mentioned  Country of Origin: USA/UK/EU/India  Country of Manufacturing: USA/UK/EU/India  Current range: The k...



SPECIFICATION

  1. Name of The Manufacturer: To be mentioned 
  2. Address of the Manufacturer: To be mentioned 
  3. Model: To be mentioned 
  4. Country of Origin: USA/UK/EU/India 
  5. Country of Manufacturing: USA/UK/EU/India 
  6. Current range: The kit should be able to inject up to 2000A or more into the primary side of the fully erected CT (height of around 10-12m from the ground) and selectable current ranges should be provided as below:- a. 0-500A, 50Hz AC Continuous b. 0-1000A, 50Hz AC Continuous c. 0-2000A, 50Hz AC Continuous 
  7. Resolution: The resolution of this primary current display should be 1A or less 
  8. Accuracy:Current measurement accuracy less than or equal to ± 0.5% of reading ± 0.5% of range 
  9. Minimum injection period: The kit should be able to inject the current continuously into the test object for at-least 10 to 15 minutes 
  10. Adjustment: The user should be able to Raise or Lower the Output Current through UP / DOWN button or similar arrangement available in the control panel of the kit 
  11. Control system: The fine control of the output current should be done through a rotating knob or similar arrangement available in the control panel of the kit 
  12. Display: The injected current into the primary side of the CT and developed current in secondary side current both must be measured and displayed in the control panel of the kit through LED / LCD display 
  13. Features: The current injection kit must comply features or characteristics as below:- 
  • Instrument should have inbuilt timer function. 
  • Instrument should have automatic Variac Zero operation at power on facility 
  • The kit can be a single unit or multiple units (Control Unit, Loading Unit and Cables & Accessories) for easy transportation and handling. 
  • Instruments must have CT Secondary current measurement facility. Range from 0 to 10A with resolution of the secondary current measurement meter should be 1mA or less with Current measurement accuracy less than or equal to ± 0.5% of reading ± 0.5% of range 
  • Kit should be sturdy, easily portable and modular type and each module weight should not exceed 50kg for easy handling. Kit can be a single unit or in two units. In case of Multiple units, each unit should not be weighing more than 50kg and total weight of the kit with all cables and accessories should not be more than 100kg. 
  • If the weight of the loading unit is less than 25kg, the output cable set should be of 2m length. If the weight of the loading unit is more than 25kg, the output cable set should be of 12m length. 
  • Necessary interconnecting cables should be supplied along with the kit. 
  • The input Power supply cable, to be supplied with the kit should be of at least 3m in length. 
  • Necessary output copper cable (multiple parallel very flexible copper cables of minimum 120mm2 cross section each) should be supplied along with the kit to carry the rated current into the CT Primary. 
  • Cable length should be sufficient to inject the required current into the Primary side of a fully erected CT (height of around 10-12m from the ground) while operating the kit from the ground level. 
  • The kit should be provided with a metallic / plastic robust enclosure. 
  • Kit shall have safety features like input supply fuses, MCBs, Power ON indications etc. 
  • The kit should be trolley / wheel mounted for easy transportation

Power Supply: Input Power Supply should be 1phase, 230Volt ±15% AC, 50Hz ± 10%Hz 

Environmental Conditions: The operating environment of the kit will be as below: a. Operating Temperature : -10°C to 50°C b. Storage Temperature : -20°C to 60°C c. Relative Humidity : Up to 95% (non-condensing) 
 