Percentage Biased Differential Relay Trainer (Electromech / Numeric)

Order Code: TPO-TRT-DIFF

Category: Electrical Machine Lab

SALIENT FEATURES Facilitates differential protection of transformer or using differential relay & characterization of different relay. Each of above trainer has built in requisite relay testing kit typically consisting of voltage injector...



SPECIFICATION

SALIENT FEATURES

  • Facilitates differential protection of transformer or using differential relay & characterization of different relay.
  • Each of above trainer has built in requisite relay testing kit typically consisting of voltage injector, current injector, elapsed time counter (1 msec resolution), trip relay logic etc.
  • The Trainer need a few set of associated relay testing (current / voltage injection etc.) panels (7-8 nos. typically) which are mounted in a light weight sturdy aluminum profile flat demo panel system. Do not need any separate testing kit.
  • Facilitates easy and safe wiring by students due to use of 4mm sturdy Shrouded banana patch cords and shrouded socket arrange-ments for high voltage circuits
  • Each panel has ABS molded plastic sturdy enclosure, and colorful screw less overlays showing circuits diagrams & its connection tag numbers for easy understanding and connection
  • Useful for Post Graduate projects and research purpose.
  • Set of Instructor Guide & Student Workbook

 

Technical Specifications

  • Input 3 phase DOL Starter panel (EMT1)
    • 4 pole MCB of 415 V/2A.
    • DOL 9A Contactor with 230V / 50 Hz / 11VA Coil .
    • Bimetallic thermal O/L relay with range 1.4A - 2.3A
    • R-Y-B Input Indicators.
    • Green SBS5 socket is provided for extend earth.
  • 1 phase AC Input supply panel (EMT16A)
    • 1ph. MCBs of 4A/1.6A - 2nos.
    • Bulb Load.
  • Variable voltage & current injector panel (EMT23A) x 2 Nos.
    • Consist of 1 phase dimmer 230VAC/1A
    • Short circuit transformer with primary 230VAC/1A,secondary 0-2-8V/12A taps
  • 3 Phase Bidirectional Power cum Energy meter panel (EMT34) x 2 Nos.
    • Bidirectional Multifunction
    • 3 phase 3/4 wire, 415VAC, CT Input 5A
    • LCD/LED display, Aux. supply 230V, 45-65Hz,5W
    • V,I, Hz, Pf, KVA, KW, KWH
    • Modbus RTU RS 485 (optional)
    • Green SBS5 socket is provided for extend earth.
  • Overcurrent & elapsed time measurement panel (EMT 39) x 2 Nos.
    • Consists of AC ammeter of 20A
    • Elapsed time counter range 999.001 sec, resolution 1msec.
  • Differential Relay Panel (EMT44/47)
    • All connection of relay are brough out on this panel
    • 2 NO Trip contacts
    • Aux. Supply 110VDC/230VAC
  • CT panel (EMT48)
    • Consist of 5/5 Amp. CT 6 Nos.
    • Primary side of CTs are brought on 3 x 2 x 2 SBS-5 sockets.
    • Secondary side of CTs are Star connectd in group of 3 & brought out on 4 x 2 SBS-5 sockets.
  • 415/230VAC, 1KVA, Star/Delta Transformer Panel (EMT49)
    • This is table top panel consisting of 415/230VAC, 1KVA, Star/Delta transformer Panel
    • All the connections of transformer primary & secondary are brought on SBS5 on the top of panel.
  • Resistor Load (EMT14B) (Table Top panel)
    • AC/DC Resistors 750E/600E/300E/212E/162E/ 125E/ 112E/100E/400W /8 taps + OFF + separate 60E tap for DC series Gen.
  • Resistive Load panel (EMT 42A/14B) (Table Top panel)
    • 3 nos of 600W resistors with switch selectable 7 nos of taps at 100, 112, 125, 150, 175, 200 & 225 Ohm
  • Protection relay type (EM/Static /Num) :
    • Electromechanical / Numerial type High speed biased differential relay, current rating 1A, with biased setting of 15%, 30% and 45% by plugboard taps, Aux. supply 110VDC

 

List of Experiments :

  1. To plot characteristics of % biased differential relay(Merz price Method)
  2. Pick up test for differential relay.
  3. Transformer protection for in zone trips faults.
  4. Transformer out zone or non trip faults.

 

Accessories :
3 Phase variac 3Amp [Optional]

 

Mechanical Dimension (mm) / Weight of Trainer :

  • 1165(L) x 300 (W) x 990 (H)
  • Net Wt. : 20 Kg. Gross Wt. : 31 kg.
  • Load Panel : Net Wt. : 20 Kg. Gross Wt. : 41 kg.

Enquiry Form