Motor Generator Set

Order Code: 22236208.3

Category: General Lab Equipment I

Motor : Type : Induction Speed : 1500 RPM 4-pole Continuous duty Class F insulation Open drip-proof selection of 50Hz 3-phase input voltages to include : 208V, 220V, 380V or 416V   Generator : ...



SPECIFICATION

  • Motor :
    • Type : Induction
    • Speed : 1500 RPM
    • 4-pole
    • Continuous duty
    • Class F insulation
    • Open drip-proof selection of 50Hz
    • 3-phase input voltages to include : 208V, 220V, 380V or 416V

 

  • Generator :
    • Type : Brushless synchronous
    • Speed : 1800 RPM
    • 4-pole
    • Continuous duty
    • Class F insulation
    • Open drip-proof selection of 60Hz
    • Output voltages to include : 120/240V
    • 1-phase
    • 120/208V
    • 3-phase or 277/480V
    • Rated at 0.8 power factor to insure proper handling of inductive loads

 

  • Mechanical Construction:
    • Motor and generator mounted on rigid steel base
    • V-belt drive system
    • Complete OSHA belt guard
    • Forkli or pallet jack provisions Standard Control Systems
    • Each motor generator set is equipped with a control panel that can be wall-mounted, door-standing or unit-mounted

 

  • The standard package includes the following components :
    • Motor Controls
    • Motor starter with adjustable overloads
    • Start-Stop push-buttons with terminal strip for remote start/stop
    • Control power transformer with fusing
    • Pilot light to indicate
    • Motor run generator controls
    • Analog meter package to include voltmeter, ammeter and frequency meter
    • Voltmeter and ammeter phase selector switches (3-phase systems)
    • Voltage regulator, ±1% regulation accuracy, with automatic buildup and rheostat for control of regulated voltage
    • Output circuit breaker, molded case, to protect, generator against short circuit or prolonged overload 
    • Pilot light to indicate 60Hz load on performance
    • Characteristics voltage regulation : ±1% from no-load to full-load at rated power factor
    • Voltage steady state stability : ±0.5% from no-load to full-load at rated power factor
    • Voltage adjustment range : ±10% in stepless increments of nominal output voltage
    • Frequency regulation : 60 Hz ±1.5% 
    • Output from no-load to full-load
    • Voltage transient : When a full-load at rated power factor is applied or released, the resultant instantaneous drop or overshoot will not exceed 30% of preset value
    • Voltage recovery time : After a full-load is applied or released, the output voltage will return to the regulaion band within 500 milliseconds
    • Harmonic distorion : Less than 3% max. total distortion factor and less than 2.5% max. single-phase when measured line-to-line

 

  • Ambient operaing conditons :
    • Temperature at 40°C
    • Relative humidity at 95% (higher temperature rating for outdoor use availabe upon request)
    • Duty cycle : Motor-generator set and controls are rated for continuous duty
    • Motor-Generator options
    • Sound-reduced enclosure
    • Weather-resistant
    • NEMA 3R enclosure
    • Casters for portability
    • Oversized generator to support motorstarting transients
    • Thermal bearing and winding protecion
    • Unit mounted control system
    • Input disconnect or circuit breaker
    • Input phase protecion relay
    • Electronic soft start for drive motor
    • Generator reconnection switch to allow selection of multiple output voltages
    • Generator over/under voltage protecion
    • Digital meter package : Remote meter package with start/stop controls protector
    • Warranty : 1 Year 
       

Enquiry Form