High Transmission Switchgear Equipment Panel

Order Code: 22236247.3

Category: General Lab Equipment II

Specification IEC/NEMA Standard HT Panel using 630A VCB and Others Accessories as per IEC requirements for HT Panel of Electric Sub-Station Steel sheet clad powder coated, dust & vermin proof, free standing, floor mounting indoor,HT Switchg...



SPECIFICATION

Specification

  • IEC/NEMA Standard HT Panel using 630A VCB and Others Accessories as per IEC requirements for HT Panel of Electric Sub-Station Steel sheet clad powder coated, dust & vermin proof, free standing, floor mounting indoor,HT Switchgear VCB 11KV, 50 HZ, 3Phsase, 630A electrolyte Copper Bus bars equipped with door locked
  • Panel Size: (H-2100mm, W-900mm, D-1000mm) Min
  • Incoming: 01 No 630 A, 11KV Braking Current 25KA (3 Sec), making Current 50KA, 50HZ
  • VCB (Fixed) Type with motor Operated mechanism with closing solenoid shunt
  • Releases: Motor Voltage 125V-150V & Shunt Opening & shunt closing 100V-130V
  • 02 Nos. Cast resin insulated Double pole, Potential Transformer ratio : 11KV/110 V
  • Class 0.5, 50VA with suitable Capacity & accurate class
  • 03 Nos. – Cast resin insulated, 11KV Dry type double core Current Transformer (CT)
  • ratio : 100A/5A/5A, for metering & Protection
  • 01 No. MCB of Adequate rating for PT Secondary Protection
  • 01 No. Ammeter 0-100A with selector switch
  • 01 No. Voltmeter 0-15 KV with selector switch
  • 01 No. Triple pole IDMT induction type Relay for over current, earth fault & short circuit protection.
  • 02 Nos. ON/OFF/TRIP Push button
  • 02 Nos. Indicating lamps ON/OFF/ TRIP
  • 01 No. Panel heater
  • 01 No. Thermostat
  • 01 Nos. every device OVERCURRENT & EARTH FAULT RELAYS, Under-Over Voltage Relay, Reverse Power Relay, Phase Sequence Relay

Terms and Condition

  • IEC/NEMA Certified VCB, Meters, Relay’s and Others accessories Installed
  • Front Door of LT Panel must be used transparent fiber/glass door fo easy visibility
  • Must be use trolley wheel system as per weight of the panel
  • LT Panel Size,Colling system,Busbar Size, Insulator’s and other 
     

Documents 

  • Manufacturers Authorization Letter submitted
  • ISO Certificate submitted
  • Catalog submitted

Accessories

  • Installed according to IEC guidelines
  • Installation & Commissioning must be done by supplier using required base for the panel, cables & others fittings
  • Warranty: 01 year warranty with service