Order Code: 24257587.1
Category: General Lab Equipment V
Voltages: Distribution: 380 V three-phase line to line frequency 50 Hz Utilization: 220V Single phase Grid transformer: Delta to star (Dy11) minimum 5KVA. Primary is matched to the incoming three-phase supply...
Voltages:
Distribution: 380 V three-phase line to line frequency 50 Hz
Utilization: 220V Single phase
Grid transformer:
Delta to star (Dy11) minimum 5KVA.
Primary is matched to the incoming three-phase supply to give the 380 V three-phase line-to-line secondary distribution voltages.
Earth link for the secondary star point.
Selectable tapping earth resistor for restricted earth fault protection tests.
Compatible with the power system simulator
Generator and prime mover:
Power class: --------------------------- 1.0
Power: minimum-------------------- 0.8 kVA
Three phase Voltage: ---------------400 V, Y
Excitation voltage: max. ------------220 V
Excitation current: max. ------------1.6 A
Frequency: ---------------------------50 Hz
Power factor: greater than---------- 0.9
Speed: minimum -------------------1500 rpm
Four pole salient pole AC generator
Brushless, with automatic and manual excitation.
Induction motor with shaft encoder and electronic four-quadrant AC vector.
Drive control, with a four-position drive inertia switch.
Mechanical data:
Type of construction: B3.
Shaft end: 1
Base: Aluminum
-Terminal box: Top
Temperature class: B (120°).
Degree of protection (IP): IP20.
Temperature detectors: Bimetal switches 110° NC (normally closed)
Generator transformer: -------Unit/Power transformer
1:1 ratio delta-to-star (Dy11) impedance matching with adjustable secondary tapping.
Transmission lines:
Three-phase model of greater than or equal 230 KV overhead transmission line for measuring steady-state operating conditions (no-load, matching, short-circuit) with the following specifications:
Quad bundle 240/40, with surge impedance 240 Ohm and natural power of max 600 MW, length150Km to 360 km. Tapping enable the carrying out of investigations at lengths of minimum 135 Km.
Scale factor: 1/1000 for current and voltage.
Length: 150 Km to 360 km
Ohmic resistance: max 13 Ohm. 8 Ohm. 5 Ohm.
Inductance: max 290 mH. 174 mH. 116 mH.
Oper. Capacity: max 5 µF. 3 µF. 2µF.
Seven (7) transmission lines representing 150KM or better
One line with four test points and dedicated three-zone distance protection.
Capacitors adjacent to the lines.
Each capacitor with selectable values and can be inserted in circuit to give pi or T-line con?gurations.
Distribution transformers:
Three phase primary 380,50hz
Two identical distribution transformers, Star-to-delta Yd1 or better
Adjustable primary tapings and matched impedances
Have variable tapings and feed a utilization bus
Dedicated relays (over current, voltage, restricted earth relays )to protect the transformers
Having connection systems to connect with other devices and testing
Switched bus bar:
Copper bus bar rode
400v/380 V system connection
Must have main bus and a standby or ‘reserve bus’
Six bi-directional feeders, each with circuit breakers
Two circuit-breakers to break each half of each bus.
Two circuit-breakers that break the coupling between the main and reserve bus.
One feeder of the bus bar must have ‘point-on-wave’ circuit breaker.
Protection relays:
Grid transformer protection
Differential
Over current
Under current
Over frequency
Under frequency and under voltage
Over voltage
Directional relay
Phase sequence relay
Feeder management relay
Thermal relay with detailed rating and features
2 x double bus protection
4 x distribution transformer protection
All the relays must be industrial standard digital protection relays compatible with all parts of the power system simulator.
All relays shall be supplied with CD ROM with compatible software and SCADA application.
Loads:
Compatible rating with the generator and transmission line
delta-connected variable resistors load----------one
delta-connected variable inductors load --------one
Delta capacitor banks--------------------------one
One load near to the generator and the other near to the distribution bus
Two sets of loads at the utilization bus; each with delta-connected variable resistors, inductors and capacitor banks.
One dynamic load (an induction motor) at the utilization bus compatible with generator rating.
Electrical supply:
Three-phase
Power output: minimum 10KW
three-wire AC input of 380 to 400 V AC 50 HZ
Standard protection system
Power factor -----above 90%
Having in built measuring system (V,I )
Fault switch
Two fault switches to apply faults
One fault switch has to be a standard three-phase switch
One has to be a timed circuit breaker with a user-programmable digital timer
Software SCADA
The software must include every feature for training purpose
Small scale for educational purpose
Virtual plant simulation:
The software shall include realistic simulations of industrial processes, complete with virtual sensors, actuators, and control systems. Users can interact with these virtual systems to learn how SCADA systems work in practice.
Interactive HMI:
The software provides a graphical Human-Machine Interface (HMI) that mimics the interface.
A real SCADA system. Users can monitor data, control processes, and respond to alarms through the HMI.
Scenario-based training:
SCADA software shall include pre-built scenarios and exercises that challenge users to troubleshoot issues, optimize processes, and make decisions based on real-time data
Data analysis tools:
The software shall include tools for analyzing historical data, trends, and performance metrics to help users understand how to interpret and use data in a SCADA system.
Networking capabilities:
Training SCADA software shall allow users to connect multiple virtual systems over a network, simulating a distributed control system environment
Security training: The software shall include modules on cyber security best practices, teaching users how to secure SCADA systems against cyber threats
Customization options: Training SCADA software often provides customization options that allow educators to create custom exercises and scenarios tailored to specific learning objectives.
Computer
All-In-One Personal Computer (desktop) with the following features:
Power input-----------------230V,50Hz
Display (Screen Size) 24 inches and above
Hard Disk Drive - 1TB hard drive size plus 500GB SSD
Processor speed - ----------------4GHz /above processor speed
Ram Memory Installed Size - --------------32GB
Processor ------------------------------------ Quad-core processor
Resolution --------------------1080p Full HD (1920 x 1080) and 2130p 4K Ultra HD (3840 x 2160).
Included Components –-----------speakers
Keyboard --128 Key Standard Keyboards to be as same brand in English.
Mouse ---Two buttons with scroll wheel optical Mouse with Mouse Pad.
Optical Drive-----SATA DVD Drive (+/-RW).
Expansion Slots ------Minimum 2 Expansion Slots including 1 Nos PCI x 16.
Network Interface-----Gigabit Ethernet Network Interface Card (10/100/1000) Internal Wi-Fi Card
I/O Ports------------- Minimum 8 USB Ports; from that at least 2 USB Ports should USB 3.2.
Minimum 1 HDMI Port
VGA Port
Operating System ------------Windows 11 Pro or Linux or Ubuntu 18.04+
Compliance and certifications ----------window certificate from original manufacturer
Monitor------ Slim shape
Should be fix a sticker with, Contact Numbers, Warranty period
This computer should be a powerful machine suitable for multitasking, gaming, video editing, and other demanding tasks. Shall have combination of SSD and HDD storage provides fast performance and ample storage space for large files and programs.
Has to include all connecting wires
Teachers and student manual
Troubleshooting manual