Diesel Engine generating set, Outdoor 30KVA

Order Code: 20213787.1

Category: General Lab Equipment II

TECHNICAL SPECIFICATIONS FOR 30kVA DIESEL ENGINE GENERATOR CHATO AIRPOT ft TECHNICAL REQUIREMENTS 1.0 INTRODUCTION This specification covers provision of Diesel Engine Generators set complete with automatic Changeover switch (ATS). The ...



SPECIFICATION

TECHNICAL SPECIFICATIONS FOR 30kVA DIESEL ENGINE GENERATOR CHATO AIRPOT ft

TECHNICAL REQUIREMENTS

1.0 INTRODUCTION

  • This specification covers provision of Diesel Engine Generators set complete with automatic
  • Changeover switch (ATS). The diesel engine generator and the generating set as a whole shall
  • be rated for 400VAC, 3phase, 50Hz, 30kVA rated prime power capacity.
  • The DEG set shall be capable of delivering 30kVA at prime power under worse case conditions.
  • 1.1 Scope of work:
  • The Specification covers supplying of Diesel Engine Generator 30kVA Prime rated @ 1500
  • rpm, 50Hz, 380-415Volts, 3phase 4 wire and 0.8 pf protected with a sound proof canopy, on
  • skid with base service fuel tank of at least 500Litres capacity, complete with all standard
  • instruments, AMF control, associated accessories and Automatic changeover Switch (ATS)
  • 1.2 Composition:
  • The Diesel Engine Generator (DEG) unit shall comprise of the following: Diesel Engine
  • Generator set, automatic transfer switch/Changeover switch (ATS), fuel tank, Exhaust system,
  • starter battery, battery charger and Outdoor whether protection and sound attenuating Enclosure.
  • Suitable rated surge arrestors (63 k amp or above) shall be provided to the mains input for
  • protection against lightning strikes.
  • The DEG hall be supplied as a complete set.

2.0 Protection

  • The engine shall be protected against low oil pressure, high engine temperature, engine
  • under/over speed, under/over voltage and cooling system failure, battery charge failure, and low
  • fuel level. Protection devices shall give visual indication and facilities for external alarm.

3.0 Diesel Engine:

  • The diesel engine shall comply with the specified International IEC standards or equivalent
  • international standards and shall be of water cooled.
  • The engine shall incorporate instrument panel with the following meters and control: -
  • a) Oil pressure — switch and gauge
  • c)Hours-run meter
  • d)Stop button
  • e)Temperature switch and gauge
  • 3.1 The engine shall be fitted with a residential type of silencer to reduce noise. Anti pollution
  • device shall be fitted in the exhaust system as optional requirement
  • 3.2 Automatic lubricating oil top up system shall be incorporated in the engine to reduce oil change
  • intervals, thus allowing maintenance intervals hours.

4.0 Cooling system

  • The cooling system shall be filled with chemically treated coolant. Rotating parts shall be
  • guarded against accidental contact in accordance with standard requirements.
  • 4.1 Exhaust system
  • The Engine shall be efficiently silenced and be complete with primary and terminal silence
  • arrangements

5.0 Control equipment for the Engine Generator

  • The control panel shall perform automatic control and monitoring of the engine generator set, .
  • Such functions shall include but not limited to the following: -
  • •Start the engine to supply AC power to the load when mains power falls outside the
  • desired value and stop the engine when mains power restored to normal condition.
  • •Stop the engine to protect it from damage when any of the protection devices is actuated.
  • •Display locally the status of engine generating and mains power condition. Among the
  • indicators shall include meters to visually monitor out-put voltage, frequency, load
  • current, starter battery charging current and voltage and hour run meter. Meters shall
  • have an accuracy of + 2% or better.
  • •Engine control shall have AMF control and remote supervision function, shall have the
  • capability of storing data.
  • 5.1 The control panel shall incorporate the under mentioned switches: -
  • a)Phase selector switches for voltmeter/ammeter for mains and generator power
  • b)Battery charge control switch
  • c)Duty selector switches (AUTOMATIC/MANUAL).
  • d)Plant control switch (OFF/TEST/MANUAL/AUTOMATIC)
  • e)Load transfer switch, electrically and mechanically interlocked.
  • f)A push button fault resets switch.
  • 5.2 Indications and Alarms.
  • The following indicators and alarms shall be provided: -
  • a)i) MAINS on LOAD light
  • ii) STANDBY LOAD indicators
  • b)Plant failure indicator lamp and alarm terminals.
  • c)MINOR alarm signal (without stopping the engine).
  • i)LOW FUEL LEVEL
  • ii)BATTERY CHARGER FAILURE
  • iii)CONTROL CUBICLE ON MANUAL CONTROL
  • iv)MAINS FAILURE
  • d) MAJOR alarm signal and engine shut down at:-
  • i)ENGINE FAILURE, after three start attempts
  • ii)LOW OIL PRESSURE
  • iii)ENGINE OVERHEAT
  • iv)ENGINE OVER SPEED, due to governor failure
  • v)FREQUENCY TOO LOW
  • vi)UNDER VOLTAGE, due to AVR. failure
  • vii)OVER VOLTAGE, due to AVR failure
  • viii)OVER CURRENT at 115%
  • x) COOLING SYSTEM FAILURE
  • The Engine shall be fitted with device which will shut off the fuel supply to the engine
  • when any of the specified alarm conditions occur.
  • 5.3 Alarm signals shall be transmitted to remote control office either individually or suitably

 