Current Transformer Test Set CT PT Analyzer-

Order Code: 23246730.9

Category: General Lab Equipment II

Full-featured to meet the excitation characteristics (ie, volt-ampere characteristics), ratio, polarity, secondary winding resistance, secondary load, ratio difference, and angle difference of various types of CT (eg, protection, metrology, TP) Such



SPECIFICATION

Main technical features

?1?Full-featured to meet the excitation characteristics (ie, volt-ampere characteristics), ratio, polarity, secondary winding resistance, secondary load, ratio difference, and angle difference of various types of CT (eg, protection, metrology, TP) Such test requirements, but also for various types of PT electromagnetic unit excitation characteristics, transformation ratio, polarity, secondary winding resistance test.

?2?Automatically give corner voltage/current, 10% (5%) error curve, accurate limit factor (ALF), instrument security factor (FS), secondary time constant (Ts), remanence factor (Kr), saturation inductance, etc.

?3?The test meets various types of transformer standards such as GB1208 (IEC60044-1), GB16847 (IEC60044-6), and GB1207, and tests are automatically selected according to the type and level of the transformer.

?4?Based on the advanced low-frequency test principle, it can deal with CT tests with inflection points up to 30KV.

?5?The device uses the international popular square wave method to make the excitation curve more perfect.

?6?Device storage capacity up to a few G, can store hundreds of thousands of test data, power loss is not lost.

?7?The test is simple and convenient, one-button CT direct resistance, excitation, ratio and polarity tests are performed, and in addition to the load test, all other CT tests use the same wiring method.

- Device panel description

Device panel structure as shown above:

·The above S1, S2 terminals: output

·Intermediate S1, S2 terminals: output voltage measurement

·The following P1, P2 terminals: Inductive voltage measurement

- The main technical parameters

Test use: CT, electromagnetic PT

Output: 0~180Vrms?12Arms?36A(peak)

Voltage measurement accuracy: ±0.1%

CT transformation ratio measuring: Range- (1~30000)

Accuracy: ±0.1%

PT transformation ratio measuring: Range: 1~20000

Accuracy: ±0.1%

Phase measurement: Accuracy- ±2min

Resolution: 0.5min

Secondary winding resistance measurement:

Range: 0~300Ω

Accuracy: 0.2%±2mΩ

AC load measurement: Range: 0~1000VA

Accuracy: 0.2%±0.02VA

working environment: temperature?-10οC~50οC?  

Humidity?≤90%