Isolation amplifier, channels A, B, C, E
Frequency range: dc to 80 kHz
Input voltage (between 0 and U)
Max 620 Vdc/460 Vac
Input resistance Ri = 1 MW in all ranges
Three?stage attenuato...
SPECIFICATION
Isolation amplifier, channels A, B, C, E
Frequency range: dc to 80 kHz
Input voltage (between 0 and U)
Max 620 Vdc/460 Vac
Input resistance Ri = 1 MW in all ranges
Three?stage attenuator: MT = 1: 1; 1/10; 1/100
Accuracy: ±2% of full scale range
Input current (between 0 and I)
Max: 10 A continuous; 16 A for t< 15 min; 20 A for t<2 min.
Internal resistance: 30 mW in all ranges
Two?stage attenuator: MT = 1 V/A; 1/3 V/A
Accuracy: ±5% of full scale range
Five outputs: A, B, C, D, E with led for over range indication
Output resistance RO: 100 W
Multiplexer: Mux channels, selectable: 1 to 8 (4 x signal; 4 x zero line)
Gain attenuator, adjustable: 0.2 to 1
Y?position, adjustable: ?8 V to + 8 V
Trigger source, switchable to A, B, C, D, E
Mux frequency, adjustable: 50 kHz to 500 kHz (typical)
Two BNC outputs for oscilloscope
Mathematical module and filter: Functional modes for channel D: Addition A+B; subtraction A?B; multiplication AxB/10 or AxB; reconstruction of the phase voltage LIN(A, B, C) from the line?to line voltages; channel E switched into channel D for multiplexing
Filter: Low pass active filter of the 2° order required for the recovery of the fundamental wave out of the PWM signals.
Cut?off frequency: 1 kHz
Space vector indicator
Voltage vector: indication with 7 led
Magnetic flux vector: BNC outputs X e Y for oscilloscope
Power supply: Single?phase from mains Frequency: 50/60 Hz